Voltage classes: safety extra-low voltage vs SELV/PELV/FELV

42/36/24/12/6V safety levels are human-contact limits; SELV/PELV/FELV are system concepts about isolation.

1. How it works

SELV = double-isolated source, unearthed; PELV = earthed; FELV = functional only, needs extra protection.

2. Practice and pitfalls

A 24V SMPS output is not SELV - wet locations need a safety isolating transformer; keep SELV wiring separated from mains wiring.

3. Concept comparison

ConceptFocusSupplyTypical use
Safety voltageContact limit42/36/24/12/6VMachine lighting
SELVIsolation+voltageSafety isolating trafoWet, confined spaces
PELVVoltage+earthReliable earthingInternal circuits
FELVFunctional onlyExtra protection neededOrdinary SMPS
Extra-low DCEnergy limitedLimited power48V telecom

4. Notes

Apply the points above to Voltage classes; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 3805, GB/T 17045, GB 5226.1, IEC 60204-1, GB/T 14821.1, IEC 60364-5-51 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Using FELV supplies where SELV is required
② Running SELV cables alongside mains in one loom
③ Judging safety by voltage number alone

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.