Where to put the thermal relay in a star-delta starter

In a star-delta starter the current halves after switching, so the relay setting must follow its mounting point or it either trips on start or misses overload.

1. How it works

There are two places to mount the relay. In the main-feed method it sits between the main contactor and the motor, carrying the line current in both start and run phases, so it is set to the motor rated current In; this is simple and common on smaller drives. In the delta-loop method it sits between the delta contactor and the winding, energised only in the running delta state, where it sees the phase current, which is In divided by √3, so it measures about 0.58 times In. The setting must follow the mounting.

2. Practice and pitfalls

Main-feed setting is 0.95~1.05 times In; delta-loop setting is 0.58 times In, so a 15A motor is set near 8.7A there. The classic error is placing the relay in the delta loop yet setting it to In, which lifts protection 1.73 times and lets the motor burn on overload; the reverse error trips on slight overload. Use a CT-fed 5A relay on large motors and pick the trip class by actual start time, 3~8 seconds typical for the changeover.

3. Star-delta relay mounting comparison

MethodPositionSetting base15A example
Main feedAfter main contactorSet to In15A
Delta loopIn delta windingSet 0.58In8.7A
CT fed5A secondary largeIn/ratio140A/300-5
Missed phaseOne loop outPhase unprotectedAll three needed
Switch surgeY to deltaRide throughClass 10-20
Common errorWrong positionWrong baseMiss or false trip

4. Notes

Rule: set the relay to whatever current its mounting point sees, In on the main feed and 0.58In in the delta loop. Draw the main circuit before retrofitting, keep all three phases connected, and let the trip class absorb the changeover surge. Simulate the no-load star-delta changeover, then load and file the method and setting.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Star-delta starting and protection per GB/T 14048.4 (IEC 60947-4-1) and GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Relay in delta loop set to In: protection 1.73 times too high, motor burns on overload
② One delta phase left out: that phase loses protection and runs single-phased
③ Wiring from memory without the circuit: method and setting mismatch, protection fails

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.