In a star-delta starter the current halves after switching, so the relay setting must follow its mounting point or it either trips on start or misses overload.
There are two places to mount the relay. In the main-feed method it sits between the main contactor and the motor, carrying the line current in both start and run phases, so it is set to the motor rated current In; this is simple and common on smaller drives. In the delta-loop method it sits between the delta contactor and the winding, energised only in the running delta state, where it sees the phase current, which is In divided by √3, so it measures about 0.58 times In. The setting must follow the mounting.
Main-feed setting is 0.95~1.05 times In; delta-loop setting is 0.58 times In, so a 15A motor is set near 8.7A there. The classic error is placing the relay in the delta loop yet setting it to In, which lifts protection 1.73 times and lets the motor burn on overload; the reverse error trips on slight overload. Use a CT-fed 5A relay on large motors and pick the trip class by actual start time, 3~8 seconds typical for the changeover.
| Method | Position | Setting base | 15A example |
|---|---|---|---|
| Main feed | After main contactor | Set to In | 15A |
| Delta loop | In delta winding | Set 0.58In | 8.7A |
| CT fed | 5A secondary large | In/ratio | 140A/300-5 |
| Missed phase | One loop out | Phase unprotected | All three needed |
| Switch surge | Y to delta | Ride through | Class 10-20 |
| Common error | Wrong position | Wrong base | Miss or false trip |
Rule: set the relay to whatever current its mounting point sees, In on the main feed and 0.58In in the delta loop. Draw the main circuit before retrofitting, keep all three phases connected, and let the trip class absorb the changeover surge. Simulate the no-load star-delta changeover, then load and file the method and setting.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Star-delta starting and protection per GB/T 14048.4 (IEC 60947-4-1) and GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.