Single-phase I=P/U; three-phase I=P/(√3·U·cosφ). Rules of thumb: 4.5A/kW at 220V, 2A/kW at 380V.
Current density 5~8A/mm² copper (derate in conduits); then verify voltage drop and protection coordination.
Motor circuits must pass the starting case: 5~7× inrush affects both drop and trip settings.
| Size mm² | Conduit rating A | 3-phase kW | Note |
|---|---|---|---|
| 1.5 | 15~16 | ~7.5 | Lighting, control |
| 2.5 | 20~25 | ~11 | Sockets |
| 4 | 30~32 | ~15 | Small motors |
| 6 | 38~40 | ~20 | Motor feeder |
| 10 | 50~55 | ~28 | Distribution |
| 16 | 65~70 | ~38 | Large loads |
Apply the points above to Quick line; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 16895.6, IEC 60364-5-52, GB 50054, GB/T 14048 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.