De-rating a contactor for frequent start-stop duty

For frequent start-stop and jogging stations a contactor cannot run at its continuous rating; it must be de-rated. Here is the basis, how much and how to select.

1. How it works

The rated current is given for AC-3 continuous running. With frequent start-stop each start takes 5~7x current and each break takes locked-rotor current, so contact heat and arc far exceed continuous, raising temperature and wear. The higher the operation rate (cycles per hour), the less cooling time, so the real carry current must drop, or life falls off a cliff and contacts may weld in service.

2. Numbers and practice

Maker catalogues give de-rating curves by operation rate; rule of thumb: hundreds per hour use AC-3 rating; 600~1200 per hour need a heavy-duty type (AC-4 or high-rate) at about 0.6~0.8 of current; above 1200 per hour consider SSR or a high-frequency contactor. Also read electrical life count backwards: frequent starts burn it fast, step up one or two sizes.

3. Pitfalls and fixes

Pit one: a jogging station sized exactly to motor Ie, tens of thousands of times a day burns quickly. Pit two: ignoring the rate, a 1200/hour rating run at 3000, contacts age early. Pit three: de-rating the contactor but not the wire, the cable becomes the bottleneck. Select a heavy-duty type or step up by actual cycles per hour, size the wire to match, SSR if needed.

4. Frequent start-stop de-rating quick table

Op rateSelectCurrent factor
Hundreds/hrAC-3 rated1.0
600~1200/hrHeavy duty0.6~0.8
>1200/hrHigh-freq/SSRDedicated
Jog stationStep 1~2 upMargin
CheckElec life countBack-select
WireMatch ratingNo bottleneck

5. Notes

Rule: frequent start-stop is not continuous current, de-rate by cycles per hour or pick heavy-duty (0.6~0.8), above 1200/hr think SSR. Jog station steps one or two up, wire sized to match, no cable bottleneck.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor duty and de-rating per GB/T 14048.4 (IEC 60947-4-1), machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Jog station sized to Ie: tens of thousands/day burns fast
② Over-rate without check: contacts age early
③ De-rating contactor but not wire: cable bottleneck

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.