Three ways electric shock happens: single phase, two phase and step voltage

Most electricians meet only the first kind in training stories, yet each shock mode has its own path through the body and its own lethality. This page compares them and states which protections actually catch which mode.

1. How it works

Single phase shock is the everyday killer: a hand touches one live conductor at 220 V and the current runs hand to feet to earth. A 30 mA residual current device can interrupt it fast enough to matter. Two phase shock is the rare but deadliest form: the body bridges two line conductors at 380 V and the current crosses chest and heart, which no RCD detects because the differential current stays balanced; only insulation, procedure and someone else nearby can save the victim.

2. Practice and pitfalls

Step voltage appears around a fallen high voltage conductor or a faulted earthing system: the ground potential difference between the two feet drives current through the legs. Keeping the stride short matters, and inside roughly 8 m of a downed 10 kV conductor the safe move is to hop on one foot or shuffle with feet together until clear. If you fall, current can cross the torso and the odds worsen sharply. Rescue discipline follows from the paths: never grab a victim still in contact, de-energize first, and treat every downed conductor as live until proven otherwise.

3. Shock mode comparison quick table

ModeVoltage enduredCurrent pathSeverity
Single phase220V phase voltageHand to feetCommon and lethal
Two phase380V line voltageHand to hand across chestMost dangerous
Step voltageGround potential differenceFoot to footWorse if you fall
High voltage stepkV class differenceFoot to footHop out within 8m
RCD coverageCatches single phase onlyNone for two phaseDistance is the barrier

4. Notes

RCDs protect against single phase shock only. Two phase shock must be prevented by insulation and procedure, and downed conductors demand single foot hopping to clear the step zone.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Shock protection follows GB/T 13870 and GB 50054, extra low voltage GB/T 3805, with safety practice per IEC 60479 and IEC 61140. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Assuming an RCD covers every scenario: a two phase shock crosses the chest with balanced current and the device never trips
② Running toward a downed conductor with normal strides: step voltage between the feet knocks the rescuer down as a second victim
③ Grabbing a shocked colleague barehanded: the rescuer joins the circuit and both need rescue

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.