A breaker that keeps tripping is not fixed by reset; trace overload, short, leakage and EMI step by step. This page gives a ten-minute locate flow.
Step one, tell which protection tripped: trips seconds after close or only under load means overload or leakage; trips instantly on close means short or leakage; random trips mean loose contact or EMI. Read the type: plain MCB (over-current) or RCBO (with RCD). If RCD, the test button simulates; see if it is the RCD. Record load state at trip (start, running, rainy) as a clue.
Step two, check by cause: overload, clamp the real current, over In means overload, reduce load or enlarge In (check cable); short, de-energise and megger, check motor/cable turn-to-earth, below 1 MΩ is a hazard; leakage, on RCD trip measure residual, shed loads branch by branch to locate; loose contact, terminal heats and trips, feel breaker temperature and tighten; EMI false trip from nearby large starters, add shielding or anti-EMI type. Trap: forcing reset on a fault burns contacts with short current.
Step three, confirm and prevent: overload reduce or replace breaker with cable check; short repair insulation; leakage find earth or replace equipment; contact tighten and use compound. After fix, run under load and watch. Prevent: periodic IR temperature and terminal tightening, monthly RCD test, size by calculated current not experience. Rule: classify, measure by item, then fix; do not blind-reset. Swap a known-good breaker to confirm a faulty unit.
| Symptom | Cause | Action |
|---|---|---|
| Trips loaded | Overload/RCD | Clamp/resid |
| Trips on close | Short/RCD | Megger |
| Random | Contact/EMI | Tight/shield |
| Rain trips | Leakage | Earth check |
| Hot trips | Loose | Tighten |
Classify first (overload/short/leakage/EMI), then measure: overload clamp, short megger, leakage shed branches, contact feel temperature and tighten. Fix by reducing, repairing, earthing or tightening. Do not force-reset a fault or burn contacts; swap a good breaker to confirm.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; distribution per GB/T 50054. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.