Oversize and you waste energy, undersize and you burn the motor; the key is the real load factor. This page shows how to estimate it from current or power and how much margin each duty needs.
The most practical method is the current ratio beta equals measured average current divided by rated current at rated voltage and frequency after warm-up. Voltage sag makes current rise for the same power, so correct for it. Constant-torque load has beta near the torque ratio, while square-law fan and pump loads need the power method because current follows speed.
For fans and pumps the shaft power P = K times flow times head over efficiency, and at 80 percent flow the power is only about 51 percent, so a VFD or two-speed arrangement saves far more than running full speed year round. Multiply the worst case by a 1.1 to 1.2 safety factor, then round up to a standard frame. Keep the usual duty in the 75 to 100 percent band for best economy; beyond 20 percent oversize the motor runs light and loses efficiency and power factor.
| Load type | Common duty | Suggested margin | Comment |
|---|---|---|---|
| Smooth continuous | 75%~100% | 10%~15% | Most economical |
| Quadratic torque | VFD regulated | 10% | Energy saving |
| Shock and vibration | Peak duty | 20%~25% | Burn protection |
| Hot and dusty | Derated | 15%~20% | Ambient |
| Frequent starts | Converted duty | Add S4 | Dedicated motor |
Estimate the real load factor by current or power first; the sweet spot is 75%~100% in daily duty. Leave a 10%~25% margin depending on environment and duty character, but never oversize into permanent light load that wastes energy. Quadratic-torque loads should get a VFD or a two-speed motor first.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor energy efficiency and sizing: GB 18613 / IEC 60034-30; safety: GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.