Selecting and wiring residual current breakers in a home distribution box

A household RCD is one component with many wrong choices: wrong rating, wrong sensitivity or neutral wired past it. This page gives the per circuit selection table and the wiring rules that keep nuisance trips away.

1. How it works

End of circuit protection for people uses 30 mA sensitivity. Lighting circuits run a 10 A breaker, general socket circuits 16 A, and air conditioning 20 to 32 A depending on the unit, all with 30 mA RCD function. The main incomer carries a selective 100 to 300 mA time delayed RCD whose job is fire prevention and backup, not personal protection, so a socket fault trips the final circuit instead of the whole house. Electromagnetic RCDs keep working when the neutral is lost and cost more; electronic ones need both lives live and are the common budget choice.

2. Practice and pitfalls

Wiring rules decide whether the device can work at all: both line and neutral of the protected circuit must pass through the RCD, the PE conductor never passes through it, and after the device the neutral must never touch earth or another circuit neutral or the differential current leaks and trips at random. Test the button monthly; if it does not trip, replace the unit. Split loads by circuit rather than relying on one big RCD, because a single 30 mA device over an entire house converts one leaky appliance into a blackout.

3. Household RCD selection quick table

PositionRated currentResidual currentPurpose
Lighting circuit10A30mAPersonnel protection
Socket circuits16A30mAPersonnel protection
Air conditioning20 to 32A30mAPersonnel protection
Main incomer63A100 to 300mAFire protection, delayed
Type choiceNone listedNone listedElectromagnetic more robust

4. Notes

Protect people with 30 mA at every final circuit and the installation with a delayed 100 to 300 mA device upstream. Route both poles through the RCD, keep PE outside it, and test monthly.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Residual current devices follow GB/T 6829 and GB 13955, with household safety per IEC 61008 and GB 50054. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Passing only the line through the RCD: the unbalanced neutral path reads as leakage and the breaker trips instantly on load
② Bonding neutral to earth downstream of the RCD: part of the load current returns through earth and trips the device at random
③ Using one 30 mA RCD for the whole house: any damp appliance blacks out every light and freezer at once

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.