I=P/U (single phase) or I=P/(√3·U·cosφ·η) (three phase); Req=U²/P at the hot operating point.
Valid directly for resistive loads; for motors and transformers the value serves power checks only - never compare with DC winding resistance.
Watch multi-voltage nameplates: connection style must match supply voltage before energising.
| Equipment | Nameplate | Calculation | Use |
|---|---|---|---|
| Heater 6kW/380VΔ | 6kW, cosφ=1 | Rph=24.2Ω | Hot check |
| Furnace 12kW/380V | 12kW | I=18.2A | Cable & protection |
| Motor 7.5kW/380V | η=0.9 | I≈16A | Power budget only |
| Transformer 10kVA | 10kVA | I=15.2A | Capacity check |
| Lamp 200W/220V | 200W | R=242Ω hot | Cold ≈1/10 |
| Adapter 65W/19V | 65W | R≈5.6Ω | Not measurable |
Apply the points above to Back; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 5226.1, GB 755 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.