Press start and the contactor is dead silent and will not seat; the fitter says no power reaches the coil. Here is the step-by-step, from supply to mechanism.
Silent no-pull splits in two: the coil gets no power (control supply off, button bad, fuse blown, wire loose), or the coil is powered but the mechanism jams (iron stuck, pole face gummed, spring broken). Step one: meter A1-A2 coil voltage. Rated voltage (≥85%Us) means power arrived, fault is mechanical; no voltage means the control loop is open, go upstream.
With power at the coil but no pull: check pole-face oil or debris, foreign object, broken shading ring, broken or jammed spring. Silent and no power: measure along stop, start, self-hold, thermal NC, fuse, control transformer; wherever voltage stops is the break. Common: blown fuse, oxidised button, loose terminal, supply pulled down by another load.
Pit one: swapping the contactor without measuring, still no pull, wasted. Pit two: poking the armature live with a screwdriver, short and shock risk. Pit three: checking only the start button and missing a stuck stop NC that stays open, never energises. Measure A1-A2 first to locate, then walk the loop point by point, strip for mechanics, always de-energised.
| Step | Measure | Judgement |
|---|---|---|
| 1 | A1-A2 voltage | Power = mechanical |
| 2 powered | Core / spring | Jam / break |
| 2 no power | Walk loop back | Fix the break |
| Common | Fuse/btn/wire | Oxide, loose |
| Stop btn | NC conducts | Stuck open |
| Work | De-energised | No live poke |
Rule: first meter A1-A2; power present check mechanism (core, spring, debris), no power walk the control loop (fuse, button, hold, thermal, transformer). Do not blind-swap or poke live, and check the stop NC for being stuck open.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control circuit and fault finding per GB/T 14048.5, contactor per GB/T 14048.4, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.