A VFD already carries electronic motor overload protection, yet many still add a bimetal relay at the output, then wonder why it trips falsely or fails to trip.
A VFD chops the output with IGBTs and has built-in current sensing plus an electronic thermal model (E.OL fault) that estimates winding temperature in real time, far more accurate than a bimetal strip and unaffected by ambient or harmonics. The standard is to let the drive protect the motor and add no thermal relay at the output. A bimetal relay there sees a non-sinusoidal current rich in high-frequency harmonics; it accumulates heat by RMS value but is sensitive to harmonics, so its characteristic drifts and only adds trouble.
Keep a relay only in rare cases: one drive feeding several motors, where the drive sees only total current and cannot detect a single overloaded motor, so each branch gets its own relay or electronic module set to that motor In with Class 10~20. Below about 10Hz the bimetal heats differently, so allow margin. If kept as redundant alarm only, set it above 1.05~1.2 times In so it alarms without cutting the run. Lower the carrier (2~16kHz typical) or add an output reactor to tame harmonics, and verify the drive protection alone before deciding on a relay.
| Case | Relay use | Setting | Note |
|---|---|---|---|
| Single drive | No relay | Drive protects | Standard |
| One-to-many | Per motor | Set to motor In | Branch protect |
| Redundant | Alarm only | 1.05-1.2In | No trip |
| Low freq | Below 10Hz | Allow margin | Heat changes |
| High carrier | 2-16kHz | Lower or reactor | Cut harmonics |
| Commission | Drive first | Confirm protect | Then relay |
Rule: no relay on a single VFD, leave protection to the drive; add branch relays only for one-to-many; if kept, alarm only. Verify electronic overload first, set by motor In, use carrier and reactor to cut harmonics, and file both settings so the two protections do not fight.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: VFD and motor protection per GB/T 12668 series and GB/T 5226.1; relay standard GB/T 14048.4. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.