The S1, S2, S3 codes on the nameplate decide whether a motor runs continuously or intermittently. This page explains the duty types and how to match the load profile so you neither overload nor oversize the machine.
GB/T 755 defines S1 to S10. S1 is continuous duty for pumps and fans. S2 is short-time, marked with a duration such as S2 30 min. S3 is intermittent periodic duty, described by the duty factor ED percent, for example 40 percent, where the same power at ED 15 percent carries more load than at ED 60 percent because cooling time shrinks. S4 adds starting, S6 is continuous periodic.
Read the load-time diagram first and compute the RMS power and peak. Continuous steady load uses S1; cyclic start-stop uses S3 or S4 matched to ED; short runs use S2. With a VFD the frame can be relaxed, but if the cooling fan is shaft-mounted its airflow drops at low speed, so fit an independent fan. Hot or outdoor sites need a further 5 to 15 percent power de-rating.
| Duty | Meaning | Typical equipment | Note |
|---|---|---|---|
| S1 | Continuous | Pumps, fans | May run nonstop |
| S2 | Short time | Gates, valves | Time limited |
| S3 | Intermittent periodic | Cranes | Watch ED% |
| S4 | Periodic with start | Machine tools | Frequent starts |
| S6 | Continuous periodic | Rolling mills | Cyclic load |
Match the real duty to the nameplate: continuous load takes S1; periodic starting takes S3/S4 with the ED% aligned. Axial fan motors on VFDs need separate cooling at low speed. Derate 5%~15% overall in hot ambients to stay safe.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Ratings and duty of rotating machines: GB/T 755 (IEC 60034-1); installation safety: GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.