How switching frequency affects motor noise and temperature

The VFD whines and runs hot because carrier frequency is mis-set. This page explains how PWM rate trades noise against heating and gives a balanced setting.

1. How it works

The VFD output is PWM chopped by the IGBT at the switching (carrier) frequency, typically 2~16 kHz, not a pure sine. Higher switching makes the waveform closer to sine, cuts harmonic current, torque ripple and noise; but every switch dissipates, so higher frequency raises IGBT and core loss and temperature. Switching frequency is a seesaw between noise and heat.

2. Numbers and practice

Motor magnetic noise comes from current harmonics and PWM forces. At 2~4 kHz the switching harmonics sit in the audible band, giving a shrill whine; raising to 10~16 kHz moves the sound above hearing, cutting noise 5~15 dB but adding heat. Trap: maxing 16 kHz for silence overheats the IGBT and derates or trips; dropping to 2 kHz for cool running fills the shop with whine.

3. Pitfalls and fixes

Rules: small drives ≤7.5 kW can run 8~16 kHz with cooling to spare; 7.5~37 kW use 4~8 kHz; >37 kW use 2~4 kHz to protect the IGBT. Hot or sealed cabinets drop another step. You can split: low frequency by day for load, high by night when light. Trap: running a non-VFD motor at high frequency invites shaft current and insulation stress; use a VFD-rated motor or output reactor/du/dt filter. Higher is not better.

4. Switching frequency guide

PowerSuggestedTrade
≤7.5 kW8~16 kHzHigh ok
7.5~37 kW4~8 kHzMiddle
>37 kW2~4 kHzCool IGBT
Hot sealedOne step downDerate
Std motorNot too highShaft current

5. Notes

Small drives can run high for silence; large must run low to protect the IGBT. Frequency is a noise-heat seesaw; drop a step in hot sealed cabinets; do not over-run a standard motor to avoid shaft current, add a reactor if needed.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Drives per GB/T 12668.2; machines per IEC 60034-1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Maxing 16 kHz for silence overheats the IGBT
② Dropping to 2 kHz fills shop with whine
③ Standard motor at high frequency harms bearings via shaft current

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.