Self-hold keeps the motor running, interlock stops forward and reverse pulling in together. Wire either wrong and the machine is uncontrolled or shorted. Here are the principles.
Self-hold (latching) lets the motor run on after the start button releases. The start NO button is paralleled with the contactor own NO auxiliary 13-14; pressing start energises the coil, 13-14 closes, and on release the current takes 13-14 to hold the coil. A stop NC button in series cuts the hold to drop the coil. The hold contact must come from that same contactor.
Electrical interlock is for mutually exclusive loops like forward-reverse, stopping both contactors pulling in together and shorting phases. In the forward coil loop you series the reverse contactor NC 21-22, and vice versa. When one pulls in its NC opens and blocks the other coil even if pressed. Mechanical interlock is a hard catch on the mechanism, double insurance. Fit both.
Pit one: taking the self-hold from another contactor, so A closes and holds B, logic scrambles. Pit two: electrical interlock only, a welded contact can still short. Pit three: wiring the interlock NC as NO, it does nothing. Self-hold from own 13-14, interlock from the other 21-22, electrical plus mechanical interlock, verify with a meter before energising.
| Item | Which contact | Effect |
|---|---|---|
| Self-hold | Own NO 13-14 | Runs after release |
| Stop | NC in series | Cuts hold |
| Interlock E | Other NC 21-22 | Blocks both-in |
| Interlock M | Mechanism catch | Even if welded |
| Fwd-rev | Double interlock | No phase short |
| Verify | Meter test | Before power |
Rule: self-hold parallels own NO, stop is series NC; interlock series the other NC. Forward-reverse uses electrical plus mechanical interlock against phase short. Meter the wiring before energising, never by memory.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Control circuit and interlock per GB/T 14048.5, contactor per GB/T 14048.4, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.