The 2 pole 4 pole on the nameplate relates to speed but many only memorise 3000 1500 without knowing why. This page gives the formula and the table so you can derive speed from frequency and poles.
Three phase async motor synchronous speed is set by supply frequency and pole pairs: n0 equals 60 times f divided by p where f is frequency in Hz and p is pole pairs. One pole pair gives the highest speed; more pairs give lower speed. The actual rotor speed is slightly below n0 due to slip.
At 50 Hz: 2 pole 3000 rpm 4 pole 1500 6 pole 1000 8 pole 750 10 pole 600. At 60 Hz multiply by 1.2. Field pitfalls: treating synchronous speed as rated speed underestimates slip by 2 to 5 percent; running a 50 Hz motor on 60 Hz supply raises speed 20 percent and may overheat; choosing wrong pole count makes the speed triple or third off the machine requirement.
| Poles | Pole pairs p | 50Hz sync | Rated about |
|---|---|---|---|
| 2 pole | 1 | 3000 rpm | 2880 |
| 4 pole | 2 | 1500 rpm | 1440 |
| 6 pole | 3 | 1000 rpm | 960 |
| 8 pole | 4 | 750 rpm | 720 |
| 10 pole | 5 | 600 rpm | 580 |
| 60Hz | x1.2 | up 20% | check heat |
Synchronous speed n0 equals 60 f divided by p; at 50 Hz 2 4 6 8 poles give 3000 1500 1000 750 rpm and rated is a few percent lower due to slip. Never use sync speed as rated in cycle calculation and watch supply frequency.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rotating machine basic parameters see IEC 60034-1 and electrical safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.