In a plant with heavy harmonics, a plain capacitor bank can make things worse instead of better: contactors burn, fuse links blow and capacitors bulge. This page explains how parallel resonance forms, how to pick the reactor ratio, and how to verify the installation before energizing it.
Capacitors and the leakage inductance of the upstream transformer form a parallel LC circuit. When one harmonic frequency lands close to the resonant point, the impedance of that branch rises sharply and the harmonic current is amplified several times, so the voltage distortion on the bus climbs. The 5th harmonic is the classic offender because its content on a typical industrial feeder reaches 3 to 6 percent, and near resonance it can be amplified beyond 30 percent. The telltale sign is a THD reading that goes up, not down, right after the capacitors switch in.
The fix is a series reactor that pushes the resonant point below the lowest harmful harmonic. The detuning ratio p equals XL divided by XC: choose 7 percent to tune near the 3.78th order and cover the 5th, or 14 percent when the 3rd harmonic is also strong. A 14 percent reactor costs you about 14 percent of capacitive output, so do not overrate without a measurement. Always scan the spectrum with a power quality analyzer before commissioning, and if an installed bank starts blowing fuses, suspect resonance first instead of simple overload.
| Item | Plain capacitor bank | 7% reactor bank | 14% reactor bank |
|---|---|---|---|
| Resonance point | Often lands near the 5th | About 3.78th order | About 2.67th order |
| Harmonics covered | Low-distortion sites only | Mainly 5th order | 3rd order included |
| Capacitive output | 100% | About 93% | About 86% |
| Risk symptom | THD rises, fuses blow | Largely suppressed | Largely suppressed |
| Cost | Low | Medium | High |
Design every compensation bank in a harmonic rich plant as a detuned type, and record the spectrum before energizing. If THD rises on an existing bank, remove the resonant step immediately and retrofit reactors.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Harmonic limits for public grids are set in GB/T 14549, low voltage reactive compensation in GB/T 15576, with installation practice per the IEC 61000 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.