Resistivity of common conductor materials with comparison table

Resistivity is a material constant; resistance adds shape. R=ρL/S.

1. How it works

Silver best, copper next, aluminium 1.6× copper, steel ~10×, NiCr alloys ~60× for heating elements.

2. Practice and pitfalls

In Ω·mm²/m at 20℃: Cu 0.0175, Al 0.028, steel 0.15; +10℃ raises copper resistance ~4%, size long runs at hot resistance.

3. Resistivity of conductors at 20℃

MaterialΩ·mm²/mvs CuTypical use
Silver0.0160.94Contact plating
Copper0.01751Busbar, cable
Aluminium0.0281.6Overhead lines
Steel0.15~0.259~14Earth rod, armour
Cast iron0.5~0.830~45Resistor elements
Constantan0.4827Shunt, sensing
NiCr alloy1.163Heater wire
FeCrAl1.480Industrial furnace
Graphite8~13460~740Brush, electrode

4. Notes

Accept cables against the standard maximum conductor resistance, not against nominal cross-section.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductor requirements per GB/T 3956, cable standards GB/T 5023/GB/T 12706. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Back-calculating cable resistance from nominal size
② Counting steel core as conducting area in ACSR
③ Sizing heater wire like copper wiring

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »