Resistivity is a material constant; resistance adds shape. R=ρL/S.
Silver best, copper next, aluminium 1.6× copper, steel ~10×, NiCr alloys ~60× for heating elements.
In Ω·mm²/m at 20℃: Cu 0.0175, Al 0.028, steel 0.15; +10℃ raises copper resistance ~4%, size long runs at hot resistance.
| Material | Ω·mm²/m | vs Cu | Typical use |
|---|---|---|---|
| Silver | 0.016 | 0.94 | Contact plating |
| Copper | 0.0175 | 1 | Busbar, cable |
| Aluminium | 0.028 | 1.6 | Overhead lines |
| Steel | 0.15~0.25 | 9~14 | Earth rod, armour |
| Cast iron | 0.5~0.8 | 30~45 | Resistor elements |
| Constantan | 0.48 | 27 | Shunt, sensing |
| NiCr alloy | 1.1 | 63 | Heater wire |
| FeCrAl | 1.4 | 80 | Industrial furnace |
| Graphite | 8~13 | 460~740 | Brush, electrode |
Accept cables against the standard maximum conductor resistance, not against nominal cross-section.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Conductor requirements per GB/T 3956, cable standards GB/T 5023/GB/T 12706. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.