Rated starting and maximum torque difference

The nameplate lists rated starting and maximum torque often mixed up; they govern different conditions and both matter for selection and start troubleshooting. This page separates the three.

1. How it works

Rated torque T_N is the continuous torque at rated voltage and rated speed corresponding to rated power T_N equals 9550 P_N over n_N. Starting torque T_st is the torque at zero speed at start. Maximum torque T_max is the peak the motor can develop usually near synchronous speed. They are three distinct operating points.

2. Practice and pitfalls

Typical async motor: T_st about 1.5 to 2.5 times T_N and T_max about 2 to 3 times T_N. At start the load must be below T_st or it will not move; during acceleration the speed passes near T_max so load peak below T_max avoids stall. Pit: selecting only by rated torque but starting torque too low for heavy belt or compressor; pit: load inertia so high that though rated is fine the acceleration peak exceeds T_max and stalls.

3. Three torque comparison table

TorqueConditionMultiple of ratedMeaning
Rated T_Nrated steady1.0steady base
Start T_stn=01.5 to 2.5can it start
Max T_maxnear sync2 to 3stall limit
Load startbelow T_stneed marginelse no move
Load peakbelow T_maxavoid stallelse crash
Pitrated onlyno startheavy fail

4. Notes

Rated T_N is the steady base torque equal 9550 P over n; starting T_st about 1.5 to 2.5 times governs whether it starts; maximum T_max about 2 to 3 times is the stall limit. Check both against load start and peak not just rated.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Rotating machine torque see IEC 60034-1 and electrical safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Selecting only by rated torque starting torque too low for heavy load
② Load peak above maximum torque stalls and overcurrent
③ Confusing starting with rated torque mis sizes the motor

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL