Slip is the single number that ties speed, torque and efficiency of an induction motor together. This page defines slip, shows two ways to calculate it from the nameplate or a measured speed, and gives typical values under load.
Slip s is the relative lag of the rotor behind the synchronous field, expressed as s equals (n0 minus n) over n0. At ideal no load the rotor almost catches the field and s nears zero; at standstill n is zero and s is 100 percent. Normal running sits in a narrow band, typically 2 to 5 percent at rated load. Larger slip means stronger cutting of the field, larger induced rotor current and more torque, but also higher slip loss in the rotor copper.
Calculate it two ways. From the nameplate, find n0 from 60 f over p, then measure n and substitute. A four pole 50 Hz machine has n0 1500; at 1440 r/min the slip is 4 percent. Alternatively measure the slip frequency fs and use s equals fs over f. Without a tachometer, compare against a healthy same pole motor; a drift of more than one or two points suggests overload or low voltage. Low supply voltage raises slip and temperature, so always judge slip at rated frequency; on a variable frequency drive read the drive displayed slip, never the raw formula.
| Poles | Sync speed | Rated speed | Rated slip |
|---|---|---|---|
| 2 | 3000 | 2940 to 2970 | 1 to 2 pct |
| 4 | 1500 | 1430 to 1480 | 2 to 4 pct |
| 6 | 1000 | 960 to 980 | 2 to 4 pct |
| 8 | 750 | 720 to 740 | 2 to 4 pct |
| 10 | 600 | 580 to 595 | 1 to 3 pct |
Treat slip as a probe of motor condition and record the rated baseline; any drift is an alarm. Calculate only at rated frequency, and on a drive read the displayed slip. Low voltage raises slip and heating, so investigate load and supply when slip departs from baseline.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Test method per GB/T 1032; rating per GB/T 755 (IEC 60034-1). Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.