MOULDLKnowledge BaseElectrical Knowledge Base3D Model DownloadsMembership
中文版Model Store »
Knowledge Base › Electrical Knowledge Base › Overall comparison and choice of motor starting methods
HomeModels
Table of contents

On this page

Electrical & Electronic Basics (600 articles)

Quick Reference

  • PLC & Programming
  • Electrical & Electronic Basics (monthly)(每月更新中)
  • Electrical Control & Drawings (monthly)(每月更新中)
  • Drives & Actuators (monthly)(每月更新中)
  • Sensors & Detection (monthly)(每月更新中)
  • Industrial Communication & Networks (monthly)(每月更新中)
  • HMI & Host Systems (monthly)(每月更新中)
  • Industrial Robots & Motion Control (monthly)(每月更新中)
  • Mechatronic System Integration (monthly)(每月更新中)
  • Fault Diagnosis & Standards (monthly)(每月更新中)

Overall comparison and choice of motor starting methods

Motor starting has direct star delta autotransformer soft starter and inverter and wrong choice either shocks the grid or fails to start. This page puts the five methods side by side and gives the choice basis.

1. How it works

How each limits current: direct start draws 6 to 8 times rated the largest shock; star delta drops start current to about one third but also torque to one third so only no or light load; autotransformer uses taps such as 65 percent 80 percent to scale voltage so current and torque both scale by the square; soft starter ramps voltage with thyristor controlling current to 2 to 4 times; inverter ramps frequency from 0 Hz giving smallest start current and controllable torque.

2. Numbers and practice

How to choose by grid and load: weak grid small transformer with large motor must limit current so choose soft starter or inverter; heavy load start compressor ball mill needs large start torque star delta insufficient use autotransformer or soft starter with kick; need speed regulation fan pump for energy saving go inverter directly; ordinary light small motor direct or star delta is most economical. Also consider start frequency: frequent starts use soft starter or inverter to protect contacts.

3. Pitfalls and fixes

Pit one: star delta with heavy load only one third torque cannot start. Pit two: treating soft starter as inverter thinking it regulates speed while it only ramps voltage. Pit three: autotransformer tap too high current not reduced enough burns transformer. Rule: weak grid plus speed need inverter; weak grid heavy start soft starter or autotransformer; light small motor direct or star delta.

4. Starting method comparison table

MethodStart currentStart torqueUse
Direct6~8xlargelight small
Star delta~1/3~1/3light load
Auto transby tap squaredby tap squaredheavy
Soft start2~4xcontrollableweak grid
Invertersmallestcontrollablesave energy

5. Notes

Weak grid with speed need choose inverter; weak grid heavy start choose soft starter or autotransformer; light small motor direct or star delta is most economical. Star delta only one third torque cannot start heavy load and soft starter cannot replace inverter speed control.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Starters see GB/T 14048.6 and electrical safety see GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① Star delta heavy load only one third torque cannot start
② Soft starter treated as inverter cannot regulate speed
③ Autotransformer tap too high current not reduced burns transformer

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »
MOULDL · Electrical Knowledge Base · free self-study reference for electrical & automation engineers, 3D CAD models at MOULDL