Relay coils come in DC12/24/48 and AC24/110/220/380V; wrong voltage means no pull-in or a burnt coil. Here is how to pick and wire.
The coil voltage must match the control supply, common DC24V or AC220V. For safety (machine tools, pendants) prefer DC24V or below AC110V, low shock risk. Panels often use DC24V from a switched supply, thin wire, small drop, good noise immunity. If only AC220V is on site, use an AC220V coil but keep voltage at or above 85%Us.
The coil terminals are A1, A2; AC has no polarity, DC must be A1 positive A2 negative or it will not pull in or burns the bridge rectifier. Many identical relays in parallel add their current; a DC24V coil draws about 0.5~1W, dozens draw several watts, size the supply. Torque terminals about 0.5~0.8N·m, crimp stranded wire.
| Item | Common | Note |
|---|---|---|
| Safe sites | DC24 / AC110 below | Low shock risk |
| In panel | DC24V supply | Small drop immune |
| AC coil | AC220V | Hold ≥85%Us |
| DC polarity | A1+ A2- | Reverse no pull |
| Parallel | Sum power margin | Stop sag |
| Torque | 0.5~0.8N·m | Crimp no slack |
Rule: coil voltage follows the control supply, use low-voltage DC for safety, read AC/DC on the nameplate. DC A1 positive A2 negative, sum parallel power with margin, crimp terminals. Measure pick-up not below 85%.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage control per GB/T 14048.5, machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.