Reversing a DC motor takes one of two routes: swap the armature polarity or swap the field polarity. The contactor sizing, the interlocking and the current at the switching instant all differ, and getting them wrong is expensive.
Armature reversal crosses the armature terminals between two contactors and leaves the field alone: simple control, but the contactors carry full armature current and must break it reliably. Field reversal swaps the small excitation current, one to five percent of rated, so tiny contactors suffice, but the flux transition is slow and a shunt machine risks a field-loss runaway if the field opens mid-switch, so it suits machines that stop before reversing. Series traction motors traditionally reverse the field, using either a double series winding or terminal re-connection.
The classic armature circuit uses KM1 and KM2 with double interlocking: the normally closed contact of the forward button in the reverse branch plus auxiliary contacts cross-wired between the coils, and neither layer may be omitted. Operationally, never reverse on the fly, since the back-EMF adds to the supply and the switching current exceeds ten times rated, welding contacts; slow down first or pass through a plugged stage, with 0.5 to 2 seconds of delay on large machines. Commission by verifying both directions at low voltage, testing the interlock with both buttons pressed, and confirming overcurrent, field-failure and zero-position protections.
| Item | Armature reversal | Field reversal |
|---|---|---|
| switched element | armature terminals crossed | field winding reversed |
| contactor rating | full armature current, large | field current only, small |
| transition time | fast, armature circuit | slow, flux reversal |
| field-loss risk | none | shunt runaway if field opens |
| typical machines | shunt, separately excited | series (traction practice) |
| interlock | button plus auxiliary contacts | stop before switching |
| procedure | slow down or plug first | stop, reverse, restart |
Reversing on the fly is the classic contactor killer; put the rule on the operating card. Test the interlocks at commissioning and every annual inspection, since welded auxiliary contacts are the usual failure shape.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 5226.1 (IEC 60204-1) for control circuits and interlocking; DC contactor utilization categories per GB/T 14048 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.