Paralleling transformers: conditions and load sharing

Three conditions: same vector group, same ratio (±0.5%), close impedance voltage (<10% difference).

1. How it works

Load shares as kVA/Z: the lower-impedance unit takes more and overloads first - check each unit's load factor.

2. Practice and pitfalls

Re-verify protection settings after paralleling; keep the size ratio within 3:1 and phase-test before closing.

3. Paralleling checklist

ConditionRequirementIf violatedCheck
Vector groupIdentical30° circulating currentNameplate
Ratio±0.5%No-load currentSecondary diff
Impedance<10% spreadUnbalanced shareuk%
Size ratio≤3:1Small unit overloadsLoad calc
PhasingMatchedClosing shortPhase test
ProtectionRe-coordinatedMisoperationStudy

4. Notes

Apply the points above to Paralleling transformers; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 15164, GB 1094, GB 50052 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Paralleling on capacity match alone
② Skipping the nameplate vector-group check
③ Leaving old settings after paralleling

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.