Three conditions: same vector group, same ratio (±0.5%), close impedance voltage (<10% difference).
Load shares as kVA/Z: the lower-impedance unit takes more and overloads first - check each unit's load factor.
Re-verify protection settings after paralleling; keep the size ratio within 3:1 and phase-test before closing.
| Condition | Requirement | If violated | Check |
|---|---|---|---|
| Vector group | Identical | 30° circulating current | Nameplate |
| Ratio | ±0.5% | No-load current | Secondary diff |
| Impedance | <10% spread | Unbalanced share | uk% |
| Size ratio | ≤3:1 | Small unit overloads | Load calc |
| Phasing | Matched | Closing short | Phase test |
| Protection | Re-coordinated | Misoperation | Study |
Apply the points above to Paralleling transformers; the figures are typical engineering values, so confirm them against the device datasheet and the actual design before release.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB/T 15164, GB 1094, GB 50052 and the corresponding IEC documents. Ratings and derating follow the device datasheet and the product design file. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.