Abnormal three-phase (lost phase, undervoltage, wrong sequence) destroys equipment; the monitoring relay is the goalkeeper. This page covers its functions, selection parameters and wiring.
A three-phase monitoring relay watches undervoltage, overvoltage, unbalance, phase loss, wrong sequence and frequency; when out of limit its output contact operates to open a contactor or alarm. It is the first protection before motors, drives and precision gear, preventing reverse run or phase-loss burn.
Select by measured voltage range such as 200 to 500 V, adjustable thresholds (undervoltage 0.8 Un, overvoltage 1.1 Un), operate delay 0.1 to 5 s to ride through dips, and one changeover contact to drive the contactor. Note self-powered versus externally powered. Wire L1 L2 L3 to the matching terminals, keep sequence right, and put the output in the contactor coil or alarm loop.
| Function | Threshold | Action |
|---|---|---|
| Under V | 0.8 Un | trip |
| Over V | 1.1 Un | trip |
| Phase loss | any lost | protect |
| Sequence | wrong acts | anti-rev |
| Delay | 0.1-5 s | ride dip |
| Output | 1 CO | drive cont |
Fit a monitoring relay ahead of important motors, drives and precision kit. Match voltage range and thresholds, take an independent reliable supply, leave output capacity margin, and before run simulate loss, wrong sequence and undervoltage to prove it acts; do not wait for a real fault to find it silent.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage devices follow GB/T 14048.5 and safety GB/T 16895. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.