ΔU=2×ρ×L×I/S round trip. 1.5mm² copper, 50m, 2A loses 2.3V (~10%).
Keep control-loop drop under 5%; check the worst-case load at the far end; SMPS output trim can compensate within 5%.
Countermeasures: bigger cross-section, distributed supplies, higher voltage, or 4-20mA current signals.
| Distance | Load 1A | Load 2A | Load 3A |
|---|---|---|---|
| 10m | 0.23V | 0.47V | 0.70V |
| 20m | 0.47V | 0.93V | 1.40V |
| 30m | 0.70V | 1.40V | 2.10V |
| 50m | 1.17V | 2.33V | 3.50V |
| 80m | 1.87V | 3.73V | 5.60V |
| 100m | 2.33V | 4.67V | 7.00V |
Tables assume 20℃; hot cabinets add ~10% resistance - keep margin.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Per GB 50054 low-voltage distribution design code. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.