With resistor, inductor and capacitor in series, the impedance is their combination. This page shows how to compute total impedance, current and phase, and why current peaks at resonance where voltage can multiply several times.
In series the total impedance is Z equals R plus j of XL minus XC, with magnitude root of R squared plus the reactance difference squared. Current I equals U over that magnitude, and the phase theta is atan of the net reactance over R. When XL exceeds XC the circuit is inductive and current lags; when XC wins it leads.
At resonance XL equals XC, so the impedance collapses to R and current peaks at U over R; this is series or voltage resonance at f zero equals one over two pi root LC. Each reactive part then carries Q times the supply voltage where Q is XL over R, so with a small R the component voltage can be tens of times the supply and insulation must allow for it.
| Quantity | Formula | Meaning |
|---|---|---|
| Impedance | root R2+(XL-XC)2 | smaller I bigger |
| Current | I = U / |Z| | max at resonance |
| Phase | theta=atan(X/R) | lead or lag |
| Res freq | 1/(2pi root LC) | f0 |
| Q factor | XL / R | voltage gain |
| Avoid | f0 not mains | stop overvoltage |
List XL and XC first, see which wins, then find the current. Compensation, filtering and tuning all use this. If current and part voltage spike at some frequency, suspect resonance, compute f0 and do not keep running until it is confirmed safe.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Circuit analysis follows GB/T 2900 and power quality GB/T 14549. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.