Star delta starting saves the grid by halving the phase voltage at start, but only if the six terminals are wired right and the changeover is timed well. This page covers the contactor logic and how to set the switch time by speed or current so you avoid arcing contacts or a failed start.
The motor brings out six ends U1 U2, V1 V2, W1 W2. At start the star contactor shorts the tails U2 V2 W2 to a star point while the heads U1 V1 W1 take supply, so each winding sees phase voltage, one over root three of line, achieving reduction. To switch, the star contactor opens first, then the delta contactor closes linking U2 to V1, V2 to W1, W2 to U1, putting windings in delta at full voltage. A tens of milliseconds interlock between star off and delta on is mandatory to prevent phase to phase short.
Timing decides success. Too early, at low speed, the switch current spikes toward a direct start with arc; too late, near rated speed, star torque is insufficient, the motor overheats and the timer wastes time. Rule of thumb: 4 to 8 seconds light load, 10 to 15 seconds heavy. Better, switch when starting current falls to about 1.2 to 1.5 times rated and stops dropping, or use a speed relay at 80 percent synchronous speed. In the field, set roughly by current then fine tune watching the start. Always enforce dual mechanical and electrical interlock, add 30 to 80 ms delay, verify the six wires are not reversed, and set the overload relay for delta running current, never star current.
| Element or param | Function | Setting |
|---|---|---|
| main contactor KM1 | feed three phase | by rated motor current |
| star contactor KM3 | short winding tails | interlock with KM2 |
| delta contactor KM2 | wind delta | interlock with KM3 |
| changeover time | sets surge and heat | 4 to 8 s light, 10 to 15 s heavy |
| overload relay | overload trip | by delta running current |
In star delta wiring keep the six end pairing and the star delta interlock, with 30 to 80 ms delay to block short circuit. Time the changeover by load and current, switching best at 1.2 to 1.5 times rated current. Set the overload for delta current, and run a no load direction check before service.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electrical safety per GB/T 5226.1 (IEC 60204-1); motor rating per GB/T 755. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.