A drive output is not a sine but a dense PWM chop, so a common meter reads it badly. This page describes the PWM shape and why only a wideband true RMS meter works.
A drive rectifies the mains to DC then chops it with IGBTs at a carrier of a few to sixteen kilohertz, producing constant-amplitude pulses whose density follows a sine; the average is the equivalent sine. On the scope you see a high-frequency dense wave rich in harmonics with very high du/dt, hundreds to thousands of volt per microsecond, which stresses motor insulation.
A cheap average meter calibrated on 50 Hz sine reads far low, often 30 to 50 percent, and drifts with carrier and modulation. A true RMS meter squares and integrates the instantaneous value, but a basic one spans only hundreds of hertz to a few kilohertz and still misses the carrier; you need a true RMS meter rated over 10 kHz for a correct reading.
| Item | Sign | Right way |
|---|---|---|
| Wave | dense HF | scope |
| Basic meter | 30-50 low | no use |
| True RMS | need 10 kHz | accurate |
| Voltage | equiv sine | wideband |
| Motor end | high du/dt | add reactor |
| Check | scope | not basic |
VFD output measurement is a top source of shop misjudgment. Keep a wideband true RMS meter and a differential probe; when output looks wrong, scope the PWM health first then read the equivalent value. A basic meter reading is only a rough hint, never for commissioning.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Adjustable speed drives follow GB/T 12668 and EMC GB/T 17626. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.