A plain breaker does not stop electric shock; you add an RCD or leakage module. Wrong position, missed neutral or never testing and the protection is only a prop.
The RCBO or RCD accessory compares line and neutral current. When a person is shocked or insulation fails, current leaks to earth, the difference exceeds the threshold (30mA domestic, time ≤0.1s) and it trips. It guards against shock and fire from leakage, not against short or overload, so a normal breaker still sits ahead or it has its own overload. Pick the rated residual current IΔn; wet areas use 10~30mA.
Fit the accessory at the very front of the protected circuit. All line and neutral of the load must leave through it, and the neutral must not be shared with another circuit or the leak is bypassed. The single-phase N must enter the device; the three-phase four-wire type needs N connected and not reversed. Torque terminals per maker (about 2.0~2.5N·m for miniature), crimp stranded wire, and snap the DIN clip fully with an audible click.
The biggest pit is never pressing the test button, so a seized mechanism goes unnoticed and will not trip on real leakage. Second, borrowing another circuit neutral splits the leakage current and the device never acts. Third, fitting one RCD after the main switch without zoning blacks out the whole shop on one fault. Press test monthly, zone the protection, keep the load neutral dedicated.
| Item | Requirement | Wrong result |
|---|---|---|
| Trip current | 30mA home, 10~30mA wet | Too high, no shock guard |
| Trip time | ≤0.1s | Too slow, kills |
| Position | Front of protected loop | Downstream not guarded |
| Neutral | Dedicated, no sharing | Leak split, no trip |
| Monthly test | Press test button | Seized mech unknown |
| N polarity | Three-phase correct | Measurement wrong |
Rule: the RCD guards at the very front, both line and neutral pass it, N is dedicated, press test monthly. Lower current in wet areas, zone the protection for easy fault finding. Re-test after any rewiring, do not trust the install-day check alone.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Residual-current devices per GB/T 16917 and GB/T 16916; earthing and shock protection per GB/T 16895 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.