The Schneider LC1D model string packs current, coil voltage and contact form; read it right to order and substitute correctly. Here is the coding rule.
In the TeSys family the format is roughly LC1D□□□. LC means contactor, 1 is AC coil (DC is LD), D is TeSys D. The digits right after are the current rating: LC1D09 = 9A, D18 = 18A, D25 = 25A, D32, D40, D65, D80, D95 up to 150A. This rating sets the main contact current; wrong means too small a horse for the load.
The suffix after current codes coil voltage and poles: B=24VDC, F=110VAC, M=220VAC, U=240VAC, Q=380VAC, D=42VDC (coding varies by generation, trust the catalogue); the trailing digits often carry auxiliary configuration and pole count (3 or 4). LC1D25M7 means 25A, 220VAC coil, 3 poles. Quote the full suffix when ordering, check item by item when substituting.
Pit one: eyeing only 25A and missing the suffix, buying a 380V coil instead of 220V, it will not pull in or burns. Pit two: same shape different generation changes auxiliary definitions, plug in and control is wrong. Pit three: substituting D series for N series (compact), mounting does not match. Use the nameplate and full catalogue model, substitute by current plus coil plus poles plus auxiliaries, consult the Schneider guide.
| Field | Meaning | Example |
|---|---|---|
| LC | Contactor | LC1D |
| 1/D | AC / TeSys D | 1D |
| Digits | Rated A | D25=25A |
| Coil code | Voltage type | M=220VAC |
| Poles | 3/4 pole | 7 often 3-pole |
| Generation | Catalogue | Check aux |
Rule: LC1D is Schneider TeSys D AC contactor, the number is rated current (09/18/25/32...), the suffix letter is coil voltage (M=220VAC etc), the tail carries poles and aux. Quote full model when ordering, substitute by current plus coil plus poles plus aux.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Contactor product per GB/T 14048.4 (IEC 60947-4-1), model naming per maker catalogue coordinated with GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.