The electricity bill carries two totals: one for the energy that did the work, one for the energy borrowed to build magnetic fields. This page separates active from reactive metering and shows how the reactive register drives the power factor charge.
The active energy meter registers P times time in kWh, the energy actually converted, and the tariff charges on it. The reactive meter registers Q times time in kvarh, the energy that oscillates between the grid and the magnetic fields of motors and transformers; it does no work yet occupies cable and transformer capacity. The ratio of the two exposes the plant power factor: tan phi equals Q over P, and the monthly average cos phi follows as P over the root of P squared plus Q squared.
Metering connections mirror wattmeter wiring: current coils in series, voltage coils in parallel; reactive meters either shift phase by 90 degrees or compute Q digitally. At month end the utility compares average power factor against the standard and applies a penalty or bonus on the bill. A reactive register that climbs much faster than history means the capacitor bank is off line, its contactors are stuck, or fuses have blown. Older electromechanical reactive meters drift badly; electronic units are far more accurate. Note that reactive registers can run backward when capacitors export vars, so wiring must follow the code to avoid lost readings.
| Item | Active energy meter | Reactive energy meter |
|---|---|---|
| Quantity | Consumed kWh | Exchanged kvarh |
| Physical meaning | Useful work done | Field energy occupying capacity |
| Billing role | Base energy charge | Power factor adjustment |
| Connection | Current series, voltage parallel | 90 degree shift or digital |
| Abnormal reading means | Consumption anomaly | Low power factor |
A reactive register growing abnormally fast points to a dead compensation bank; check the power factor line on the bill first, then the bank. Prefer electronic meters for accuracy.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Energy metering follows the GB/T 17215 series, power quality and tariff adjustment GB/T 12325, compensation equipment GB/T 15576. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.