Key points for selecting Schneider iC65 breakers

The iC65 is the most common imported MCB in projects, with dizzying options. This page covers the key selection points and common traps.

1. How it works

The iC65 family has breaking ratings iC65N (6 kA), iC65H (10 kA), iC65L (15 kA), plus residual combination (iC65+Vigi). First set breaking: end circuits use N 6 kA, near-transformer or feeders use H/L. Rated 230/400 V, 1~63 A, curves C/D (also K for transformers, Z for semiconductors). Poles 1P~4P and 1P+N.

2. Numbers and practice

Beyond standard C/D, iC65 has K (magnetic 10~14 In, for transformers and high-reactance solenoids) and Z (2~3 In, sensitive for semiconductors). Motor circuits still use D or K. Point: choose curve by load, do not use all C. Rich accessories: auxiliary OF, fault alarm SD, shunt MX, over-voltage, Vigi residual module (30/100/300 mA adjustable).

3. Pitfalls and fixes

Selection flow: compute load current for In (1.0~1.25× resistive, 1.5~2.5× motor) → curve by load (C resistive, D/K inductive) → breaking class by fault point → poles (2P single, 3P three) → Vigi or accessories as needed. Traps: L class at end wastes money while N at a big fault point is unsafe; all-C trips motors on start; Vigi neutral must be wired right and not re-grounded. Rule: breaking to point, curve to load, poles to circuit, RCD to place.

4. iC65 selection

PointValueNote
BreakingN6/H10/L15kBy fault
CurveC/D/K/ZBy load
Current1~63 ABy load
Poles1~4P2P single
RCDVigi30/100/300

5. Notes

iC65 breaks into N(6 kA)/H(10 kA)/L(15 kA); end uses N, big-fault uses H/L. Curves C/D standard, K for transformers/solenoids, Z sensitive, motors D/K. Set In by load, breaking by fault, Vigi RCD by place (30/100/300 mA). All-C trips motors.

6. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; MCB per IEC 60898. Always check the device datasheet and the product design file for ratings and derating.

7. Cautions

⚠️ Three common pitfalls:
① L class at end wastes; N at big fault unsafe
② All-C trips motors on start
③ Vigi neutral mis-wired or re-grounded mis-trips

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.