A loosely terminated breaker terminal trips hot or burns the panel. This page covers wire choice, torque and crimp pitfalls.
Breaker terminals are rated for a conductor size (e.g. 1~25 mm²) and need matching copper wire; aluminium needs special or transition lugs. Stranded wire must be crimped into a lug (OT/UT) before clamping, never fanned directly in (virtual contact, overheating). Strip length is moderate so the conductor just enters and insulation does not hit the screw. Traps: stranded without lug loosens and overheats; oversize wire forced in gives too little contact area and heats.
Torque matters: terminals have specified torque (sample, e.g. M5 2.5~3.5 N·m, M8 ~8~10 N·m); too low raises contact resistance and heat, too high crushes the conductor or strips threads. Use a torque screwdriver/wrench, never by feel. Reference: copper connection torque by size, 16 mm² ~5 N·m, 35 mm² ~8 N·m. After tightening, pull the wire to confirm it holds. Trap: feel-tightening loosens with thermal cycling and goes virtual.
Steps: right lug and size → strip and crimp (matching die) → insulate → torque to spec → pull and IR-temperature verify. Periodically IR-check terminal temperature; above 60℃ or >30 K over ambient needs tightening. Multiple wires in one terminal need a distribution block, never crammed. Rule: right wire, crimped lug, correct torque, pull-proof, temperature-checked. Manuals say re-tighten terminals yearly.
| Size | Torque | Point |
|---|---|---|
| 1.5~4 mm² | 1.2~2.0 N·m | Small lug |
| 6~16 mm² | 2.5~5 N·m | Crimp |
| 25~35 mm² | 5~8 N·m | M6 |
| 50 mm² | 8~12 N·m | M8 |
| Verify | Pull, temp | ≤60℃ |
Pick copper by rated terminal size; stranded must be lugged, never fanned. Torque to spec with a tool (16 mm²≈5, 35 mm²≈8 N·m); low heats, high crushes. After tighten, pull and IR-check (above 60℃ or >30 K tighten). Never cram multiple wires in one hole.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Switchgear per GB/T 14048.2; termination per GB/T 5273. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.