After new install or overhaul, insulation testing decides whether equipment will leak or arc. This page covers megger selection, three-phase winding test and the standard limits.
Use an insulation resistance tester, the megger, with voltage rated to the equipment: 500 V for low-voltage gear up to 500 V, 1000 or 2500 V for high voltage. Digital types with timed reading are steadier. The equipment must be de-energized and discharged; large capacitors like cables and motors need thorough discharge or they hurt you and read falsely low.
For a motor, test each phase to frame with the other two shorted to earth, line terminal on the winding and earth on the frame; the reading should exceed the rule, generally 0.5 megohm for low-voltage motors and 1 megohm for critical kit. Test between phases too, and cables between conductors and screen, transformers between windings and to earth.
| Item | Method | Standard |
|---|---|---|
| Meter | 500V if 500 | higher if HV |
| To frame | phase-shell | >=0.5 M |
| Between | 2 ph-other | same |
| Absorb | R60/R15 | >=1.3 |
| Discharge | thorough | safe |
| Read | timed | digital |
Insulation testing is the safety gate before energizing; do it on new, damp, idle or overhauled equipment and log trends so a sudden drop flags latent fault. Do not scrap on a low damp reading, dry and retest. Use the right megger voltage and wiring, and discharge properly afterward.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Commissioning follows GB/T 50150 and machine safety IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.