Diagnosing a residual current breaker that keeps tripping

A tripping RCD is a symptom, and swapping in a bigger one just silences the alarm. This page gives the sequence that separates genuine leakage from wiring mistakes and damp insulation, without guessing.

1. How it works

First decide whether the trip is real protection or a fault of its own. If the breaker trips the instant you try to reset with everything disconnected, the device itself or its wiring is bad. If it resets but trips when a specific appliance starts, that appliance leaks. If it trips at random times, suspect neutral to earth contact somewhere: a shared neutral from another circuit, a nail through a cable, or water in a junction box. Electronic loads with EMC filters leak a few milliamperes each by design, and a dozen of them in parallel add up to a standing trip.

2. Practice and pitfalls

Work by division: open the main, disconnect all final circuits, reset, then reconnect one circuit at a time until the trip returns, and narrow further by unplugging loads. Measure insulation with a 500 V megger on the suspect circuit; anything under 0.5 megohm to earth will trip a 30 mA device sooner or later. Damp bathrooms and outdoor sockets dominate the statistics after rainy seasons. Never solve it by fitting 100 mA devices everywhere, because protection for people depends on that 30 mA figure.

3. Tripping diagnosis quick table

SymptomLikely causeAction
Trips immediately on resetFaulty device or wiringReplace or inspect wiring
Trips with all loads offDevice failureReplace the RCD
Random tripsNeutral earthed somewhereSeparate N and PE
Trips in wet weatherInsulation soakedDry out and retest
LED circuits tripAccumulated filter leakageUse high immunity type

4. Notes

Isolate, then re-energize circuit by circuit to localize the leak, and verify with a 500 V megger. Neutral to earth mixing and damp insulation cause most random trips; never raise the sensitivity to hide them.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Residual current protection follows GB/T 6829 and GB 13955, insulation testing GB 50150, with devices per IEC 61008. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Swapping a 30 mA device for 100 mA to stop the trips: personal protection is lost and the real leak keeps growing
② Hunting the fault without disconnecting circuits first: hours wasted guessing instead of five minutes of division
③ Ignoring a neutral shared with another circuit: standing current returns through earth and trips the RCD without any real fault

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.