Thermal overload relays: how the bimetal strip works

Before an overloaded motor cooks its windings, the thermal relay should trip first. It senses overcurrent with a heated bimetal strip that bends and releases a latch, simple and dependable. This page explains the strip principle, the three-phase differential design and temperature compensation.

1. How it works

The bimetal strip is two metals of different expansion coefficients rolled together. Line current flows through it or through a heater alongside it; heat bends it toward the low-expansion side until it pushes the trip latch, opening the NC contact and dropping the contactor coil. Higher current bends it faster, giving the inverse-time characteristic: about 20 minutes at 1.2 times setting, 2~3 minutes at 1.5 times, 5~15 seconds at 6 times. That curve sits above the motor starting current of 5~7 times, so starts pass, while sustained overload trips first.

2. Practice and pitfalls

Three-phase relays link three strips, or route them through a differential mechanism. A balanced overload bends all three together and trips normally; on phase loss two strips overheat while one does not, and the differential mechanism amplifies the displacement and trips early, which is vital because single-phasing is the top killer of motors on site. A compensated strip cancels ambient effects across roughly -25~55℃, though settings should still be corrected for the actual panel temperature.

3. Thermal relay operating characteristic reference

Current multipleTrip timeMeaningField action
1.05xNo trip within 2hNormal allowanceRun as usual
1.2xWithin 20 minLight overloadCheck load swings
1.5x2~3 minSustained overloadStop and inspect
6x5~15 sStart or stallVerify start time
Phase lossDifferential early tripSingle-phasingStop, check wiring
High ambientCharacteristic shiftsPoor ventilationCorrect for panel temp

4. Notes

Rule: current heats the strip, the strip bends, the inverse-time curve sits between start and damage; differential action guards phase loss, and every trip gets a cause hunt before reset. Put the test button into routine rounds, because a stuck relay means an unprotected motor.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Thermal overload relays per GB/T 14048.4 (IEC 60947-4-1); motor thermal protection per GB/T 12350 and the IEC 60034 series. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Resetting and restarting without finding the cause: an unresolved stall or lost phase burns the motor within a few cycles
② Never exercising the test button: a jammed mechanism goes unnoticed and the motor runs unprotected at overload
③ Settings twisted by hand over time: the calibration drifts, nuisance trips or missed trips follow, keep records and recheck

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.

Related reading

Related 3D models: Ready to build it? Download free 3D models & CAD drawings at MOULDL »