Before an overloaded motor cooks its windings, the thermal relay should trip first. It senses overcurrent with a heated bimetal strip that bends and releases a latch, simple and dependable. This page explains the strip principle, the three-phase differential design and temperature compensation.
The bimetal strip is two metals of different expansion coefficients rolled together. Line current flows through it or through a heater alongside it; heat bends it toward the low-expansion side until it pushes the trip latch, opening the NC contact and dropping the contactor coil. Higher current bends it faster, giving the inverse-time characteristic: about 20 minutes at 1.2 times setting, 2~3 minutes at 1.5 times, 5~15 seconds at 6 times. That curve sits above the motor starting current of 5~7 times, so starts pass, while sustained overload trips first.
Three-phase relays link three strips, or route them through a differential mechanism. A balanced overload bends all three together and trips normally; on phase loss two strips overheat while one does not, and the differential mechanism amplifies the displacement and trips early, which is vital because single-phasing is the top killer of motors on site. A compensated strip cancels ambient effects across roughly -25~55℃, though settings should still be corrected for the actual panel temperature.
| Current multiple | Trip time | Meaning | Field action |
|---|---|---|---|
| 1.05x | No trip within 2h | Normal allowance | Run as usual |
| 1.2x | Within 20 min | Light overload | Check load swings |
| 1.5x | 2~3 min | Sustained overload | Stop and inspect |
| 6x | 5~15 s | Start or stall | Verify start time |
| Phase loss | Differential early trip | Single-phasing | Stop, check wiring |
| High ambient | Characteristic shifts | Poor ventilation | Correct for panel temp |
Rule: current heats the strip, the strip bends, the inverse-time curve sits between start and damage; differential action guards phase loss, and every trip gets a cause hunt before reset. Put the test button into routine rounds, because a stuck relay means an unprotected motor.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Thermal overload relays per GB/T 14048.4 (IEC 60947-4-1); motor thermal protection per GB/T 12350 and the IEC 60034 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.