Measuring insulation resistance of electrical equipment and the pass criteria

The megger reading decides whether a motor runs another year or cooks its windings next week. This page covers tester selection by voltage class, correct procedure, and the pass values including the absorption ratio test.

1. How it works

Pick the tester voltage from the equipment rating: 500 V for low voltage circuits and motors, 1000 V for machines up to 1 kV, and 2500 V for medium voltage cables and transformers. Discharge and isolate the object first, and on cables or long windings let the charge bleed off afterward because a stored charge bites hours later. Keep the guard terminal in use on damp or dirty surfaces so surface leakage does not flatter the reading.

2. Practice and pitfalls

Apply the voltage for a full minute before reading. Pass values: low voltage circuits and wiring at 0.5 megohm or better, low voltage motors at 1 megohm, and larger machines also require an absorption ratio, the 60 second reading divided by the 15 second reading, of 1.3 or more; a dry healthy insulation climbs steadily while a wet one stays flat. Convert readings to a 75 degree reference when comparing over time, because insulation resistance roughly halves for every 10 degree rise. Trend matters more than any single number: a motor that reads 100 megohm every year and suddenly reads 5 is failing regardless of the pass line.

3. Insulation resistance pass criteria quick table

EquipmentTest voltagePass criteria
Low voltage wiring500V0.5 megohm or more
Low voltage motor500V1 megohm or more
1kV class motor1000V1 megohm plus absorption 1.3
Power cable1000 to 2500V0.5 megohm per km or more
Transformer2500VAbsorption ratio 1.3 or more

4. Notes

Choose the megger voltage by rating, record temperature and convert to 75 degrees for comparison, and require absorption 1.3 or better on windings. Trend the readings year over year.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Commissioning tests follow GB 50150, resistance measurement methods GB/T 3048, with low voltage practice per GB 50054 and IEC 60364. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Megger testing a motor fresh off line without discharging: stored capacitive charge bites the next person who touches the terminals
② Reading at 15 seconds and leaving: a wet insulation passes the snapshot while the absorption test would have failed it
③ Comparing summer and winter readings directly: resistance halves per 10 degrees and a healthy trend looks like decay

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.