It is current, not voltage, that stops a heart, and the dose is a product of amplitude and time. This page lays out the injury mechanisms, the fibrillation thresholds, and the protection logic that follows from them.
Electric current harms in three ways: heating at contact points, tetanic contraction that freezes the hand on the conductor, and disturbance of the heart rhythm. Between roughly 6 and 10 mA the muscles spasm and the victim cannot let go; beyond that the current climbs toward the fibrillation region. Ventricular fibrillation, the usual cause of death, depends on both amplitude and duration: near 50 mA for a second, or 100 mA within 0.2 to 0.3 seconds, the synchronized pumping rhythm collapses into useless quivering.
Curiously, very large currents above several hundred amperes applied for a fraction of a second can clamp the whole heart and allow resumption on release, which is why defibrillators work, but nobody should bank on that in the field. The protection logic follows directly from the dose: limit current with 30 mA residual current devices and limit duration with fast interruption inside 0.1 s, which is why RCD trip time and breaker clearing time both matter. After a shock, cut the power before touching the victim, then start CPR immediately; brain damage begins around 4 minutes without circulation, so the rescue window is brutally short.
| AC current | Duration | Effect |
|---|---|---|
| 0.5 to 1mA | Any | Perception, tingling |
| 6 to 10mA | Any | Cramp, cannot let go |
| 50mA | Over 1s | Fibrillation risk |
| 100mA | Over 0.1s | Highly dangerous |
| Above 200mA | Brief | Cardiac arrest, possibly reversible |
Protection combines a 30 mA RCD for current and fast clearing for time. Always cut power before rescue, then CPR without delay, because the brain survives roughly 4 minutes without circulation.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Current effects on the body are detailed in GB/T 13870.1 and GB/T 13870, extra low voltage GB/T 3805, with reference to IEC 60479. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.