Soft stop eases down, e-stop locks now; they serve different goals and must not be mixed. This page covers logic, devices and safety level.
Soft stop ramps the motor down over a set slope (10~30 s) via VFD deceleration or soft-starter voltage drop, to cut water hammer, mechanical shock and spillage; it is a process stop, not time-critical, set by inertia. Use it on pumps to avoid hammer, long belts to avoid pile-up, fans to avoid surge. Soft stop is normal shutdown procedure, not safety protection.
Emergency stop is a safety function that per GB/T 5226.1 must remove danger as fast as possible via a hardware loop (e-stop button plus safety relay/contactor), responding in hundreds of milliseconds, ignoring comfort. It is category 0 (immediate de-energise) or 1 (controlled then de-energise). The e-stop circuit must be hard-wired, dual-channel and immune to PLC software failure.
Differences: soft stop is software/parameter and can be overridden by logic; e-stop is an independent hardware safety loop. Soft stop is slow, e-stop fast. Soft stop protects equipment, e-stop protects people. Traps: wiring e-stop to only trigger soft stop leaves a fatal十几秒 delay; using soft stop as e-stop lets water hammer burst pipes; after e-stop a high-inertia machine still coasts and hurts without a mechanical lock. Rule: safety goes hardware e-stop, process comfort goes soft stop.
| Item | Soft stop | E-stop |
|---|---|---|
| Purpose | Smooth process | Person safety |
| Response | Seconds | Milliseconds |
| Realisation | Parameter | Hardware loop |
| Safety func | No | Yes (GB/T 5226.1) |
| Typical | Pump belt | Accident lock |
Soft stop is a parameter process stop; e-stop is a hardware safety loop in milliseconds. Never substitute soft stop for e-stop or the delay kills. Lock high-inertia machines after e-stop. Safety uses e-stop, comfort uses soft stop.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Machinery safety per GB/T 5226.1; e-stop per IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.