A time relay provides the delay decision and an interface relay provides the contacts: together they are the cheapest way to delay an output or a return. This page shows how to wire on-delay and off-delay combinations and how to set the timing.
The time relay KT makes the timing decision, the interface relay KA executes it. A KT contact is a single, small pair rated roughly 3~5A; driving a contactor coil or several loads directly wears it out fast. Let the KT contact drive the KA coil instead, then let two to four KA contacts distribute the loads: lamps, buzzers and interlock signals each get their own contact and none drags the others down, so a fault stays contained.
On-delay: the KT coil starts timing when the signal arrives, the contact closes after the set time and resets the instant the signal drops, good for warm-up and sequenced starts. Off-delay: the contact operates immediately on energising and returns some time after the signal drops, good for run-on lubrication or fans. Common settings span 0.1s to 60s with repeat accuracy of about ±2%~±5% on electronic types, and note that an electronic KT needs 100~200ms of power-off time to reset, so a shorter pulse leaves it unreset and the next cycle drifts.
| Requirement | Configuration | Sequence | Setting guide |
|---|---|---|---|
| Sequenced start | On-delay KT + KA | Delay after signal, then KA in | 2~10s per process |
| Run-on after stop | Off-delay KT + KA | KA holds after signal drops | 30~120s lubrication |
| Contact expansion | KA multi-contact split | KT drives KA, KA splits loads | Under 5A per contact |
| Alarm signalling | KA NO drives lamp/buzzer | Taken parallel with load | AD16 lamp 0.5~2W |
| Interlock delay | KT NC in the other leg | Stop first, then start | 0.5~2s delay |
| Commissioning | Stopwatch or PLC trace | Verify timing step by step | Within ±5% repeat |
Rule: the KT times, the KA executes, and the KT contact only pushes the KA coil. Be clear about on-delay versus off-delay before wiring, commission single units before linking, and check that the signal width exceeds the KT reset time, otherwise the sequence is right one cycle and wrong the next.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Time relays and relay contacts per GB/T 14048.5 and GB/T 21711.1; machinery safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.