An under-voltage release is the breaker's blackout watchdog: it trips the breaker when supply voltage falls below a set threshold, so machines do not auto-restart after a power loss.
The release coil stays connected across the control supply. Above about 85% of rated control voltage Us the armature holds and the breaker can be closed; between 35% and 70% Us the armature drops and the breaker opens. It is passive and voltage-sensing, unlike a shunt trip that needs a pushbutton signal. Use it to stop a motor from restarting on return of supply and to cut a motor stalling under low voltage.
The coil voltage must match the control supply: AC230V, AC400V, DC24V or DC110V. Wire it to the line side or the transformer secondary, never to a point downstream of a contactor holding circuit, or it stays energised during a blackout and loses its purpose. An AC 220V coil draws 8~15VA; torque terminals to the maker figure, about 1.2~1.7N·m, since a loose screw heats and causes spurious trips.
Never short or remove the release for convenience. After a brownout the machine restarts on its own while someone is inside it. Also tap the supply ahead of the contactor; a tap after the contactor gives a false powered-but-will-not-close fault. An AC coil buzzing below 70% Us is overheating and should be replaced.
| Item | Normal | Action |
|---|---|---|
| Pick-up and hold | ≥85% Us | Below this it will not close or trips |
| Drop-out trip | 35%~70% Us | Must open within this band |
| Coil voltage | AC230/400, DC24/110 | Must match control supply |
| Supply tap | Line side or xfmr secondary | Never downstream of contactor |
| Coil power | 8~15VA (AC) | Right wire size, correct torque |
| Abnormal noise | Buzz below 70% Us | Check voltage or replace coil |
Rule of thumb: the release is the blackout watchdog, correct coil voltage, supply tap upstream, never jumper it. Before energising confirm it is fitted; if removed for service, tag it and measure drop-out voltage after refit. Fit it on critical, unattended or personnel-access equipment.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage switchgear general rules per GB/T 14048.1; circuit-breaker standard per GB/T 14048.2; machine safety per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.