Thermal overload trip: reset procedure and inspection checklist

Resetting a tripped overload relay without finding the cause is the fastest way to burn a motor. This page gives a short field checklist to run before you touch the reset lever.

1. How it works

Before reset, feel the case: hot means sustained overcurrent. Inspect terminals for discolouration, sniff for insulation smell, and clamp-meter all three phases against the nameplate. If the load is jammed or a belt is overtensioned, resetting only drives the current straight back up, and repeated overheating permanently shifts the bimetal calibration.

2. Practice and pitfalls

After the cause is cleared, press the blue TEST/RESET lever twice on manual types - first to trip, then to reset - with contacts 95-96 returning closed. Automatic types recover in 2 to 5 minutes as the bimetal cools, but never use auto-reset where remote restart is hazardous. After reset, jog the motor and watch the ammeter before applying load.

3. Trip cause quick table

SymptomMost likely causeAction
Trips again within minutesReal overload or phase lossClamp all three phases vs nameplate
Reset lever will not pressBimetal hot or mechanism jammedWait 10 minutes, never force it
Trips at every startSetting too low or stalled loadCheck dial against nameplate
Frequent trips, normal currentLoose terminal heating the relayTorque power terminals, check temp
Phase currents differ over 10%Burnt contactor tipsMeasure contactor voltage drop
Trips in summer onlyAmbient compensation limitLower setting or improve ventilation

4. Notes

Rule of thumb: feel, look, measure current, clear the cause, reset, jog, watch. A trip is the relay doing its job - hammering reset with the fault still present removes the last line of defence for the motor.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overload protection per GB/T 14048.4; machine electrical safety per GB/T 5226.1 / IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Reset without diagnosis:locked-rotor current is six times rated, windings smoke in minutes
② Auto-reset on a remote circuit:the drive restarts itself with the fault still there
③ Forcing the lever:bent mechanism, drifting trip point, protection gone

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.