Resetting a tripped overload relay without finding the cause is the fastest way to burn a motor. This page gives a short field checklist to run before you touch the reset lever.
Before reset, feel the case: hot means sustained overcurrent. Inspect terminals for discolouration, sniff for insulation smell, and clamp-meter all three phases against the nameplate. If the load is jammed or a belt is overtensioned, resetting only drives the current straight back up, and repeated overheating permanently shifts the bimetal calibration.
After the cause is cleared, press the blue TEST/RESET lever twice on manual types - first to trip, then to reset - with contacts 95-96 returning closed. Automatic types recover in 2 to 5 minutes as the bimetal cools, but never use auto-reset where remote restart is hazardous. After reset, jog the motor and watch the ammeter before applying load.
| Symptom | Most likely cause | Action |
|---|---|---|
| Trips again within minutes | Real overload or phase loss | Clamp all three phases vs nameplate |
| Reset lever will not press | Bimetal hot or mechanism jammed | Wait 10 minutes, never force it |
| Trips at every start | Setting too low or stalled load | Check dial against nameplate |
| Frequent trips, normal current | Loose terminal heating the relay | Torque power terminals, check temp |
| Phase currents differ over 10% | Burnt contactor tips | Measure contactor voltage drop |
| Trips in summer only | Ambient compensation limit | Lower setting or improve ventilation |
Rule of thumb: feel, look, measure current, clear the cause, reset, jog, watch. A trip is the relay doing its job - hammering reset with the fault still present removes the last line of defence for the motor.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overload protection per GB/T 14048.4; machine electrical safety per GB/T 5226.1 / IEC 60204-1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.