Live work is about holding three lines at once: distance, equipment and supervision. This page lists minimum clearances by voltage and the PPE kit that actually protects.
Minimum distances to live parts are hard rules: 0.7m at 10kV, 1.0m at 35kV, 1.5m at 110kV, 3.0m at 220kV; with barriers, 10kV drops to 0.35m. Low voltage work keeps 0.1m plus insulation. These are not estimates - below the limit, 10kV arcs across air without contact. Long metal objects like ladders and pipes must be checked for their full swing radius, because the moment of tipping is the moment of contact.
Low-voltage kit: class-tested insulating gloves and overshoes, long-sleeve cotton clothing, insulating matting, tools with 100mm-plus insulated shanks, and a proven voltage detector. Test intervals: gloves and overshoes every 6 months, poles yearly, detectors every 6 months - inflate-test gloves for pinholes and retire anything scored. Discipline: one dedicated observer who does nothing else, one-hand operation with the free hand behind the back, re-verify before resuming after any interruption. No live work in rain, damp, from metal ladders, or tired.
| Voltage level | No barrier | With barrier | Main protection |
|---|---|---|---|
| 380/220V LV | 0.1m | Barrier work allowed | Gloves, matting, tools |
| 10kV | 0.7m | 0.35m | Insulated pole, observer |
| 35kV | 1.0m | 0.6m | Pole, barriers |
| 110kV | 1.5m | 1.0m | Specialized methods |
| 220kV | 3.0m | 2.0m | Certified live-line crew |
| 500kV | 5.0m | 3.5m | Certified live-line crew |
Before touching anything: observer in place, detector proven, clearance calculated. Check test labels and glove condition; refuse metal ladders, wet hands and storms. Every rule here was written after an accident - shortcuts just copy it.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Electric power safety work rules per GB 26860; preventive testing of insulating tools per DL/T 976; shock protection per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.