Inductive kickback from motor and relay coils: causes and suppression

The moment a contactor opens, the coil spikes to hundreds of volts - and PLC transistor outputs and small relay contacts pay the bill. This page explains the kickback and the fix for every load type.

1. How it works

Inductor current cannot change instantly. Cut it and U = L·di/dt produces spikes 10 to 30 times the supply: a DC 24V relay coil swings ±200 to 400V for tens of microseconds. Victims: PLC transistor outputs rated 50V, arcing relay contacts, and any electronics sharing the supply. In cabinets full of drives and servos, unexplained output failures trace back to this more often than to anything else.

2. Practice and pitfalls

DC coils take an anti-parallel flyback diode, clamping the spike to −0.7V at the cost of a 5 to 15ms release delay; when fast release matters, a 33 to 39V zener in series with a diode clamps at −36V and releases within 2ms. AC coils cannot share a diode (it would conduct on both half-cycles) - fit an RC snubber, 0.1 to 0.47µF X2 in series with 100 to 470Ω, directly across the coil terminals, and another across contacts that break inductive loads.

3. Kickback suppression quick table

Load typeSuppressorValuesResult
DC24V relay coil1N4007 flyback diodeCathode to positive−0.7V spike, 5~15ms release
DC24V fast release33~39V zener + diodeSeries, anti-parallel−36V clamp, under 2ms
AC220V contactor coilRC 0.47µF X2 + 330ΩAcross coil terminalsSpike within 2x supply
Contact breaking loadRC 0.1µF + 100ΩAcross the contactLess arcing, longer life
PLC transistor outputOne of the above, alwaysMatch the loadOutput life doubles
Solenoid DC coilDiode or varistor 14DClamps near 40VSimple and robust

4. Notes

Cabinet motto: every coil gets a suppressor - diodes for DC, RC for AC - mounted at the coil terminals, not the far end of the terminal rail. When PLC outputs die in batches, find the naked coil first.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overvoltage protection in control circuits per GB/T 5226.1 (IEC 60204-1); varistor specification per GB/T 10193. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① No flyback diode on a DC coil:PLC outputs die in batches from repeated overvoltage
② A diode alone across an AC coil:it conducts both half-cycles, a dead short
③ Snubber mounted far from the coil:lead inductance ruins the clamp

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.