The moment a contactor opens, the coil spikes to hundreds of volts - and PLC transistor outputs and small relay contacts pay the bill. This page explains the kickback and the fix for every load type.
Inductor current cannot change instantly. Cut it and U = L·di/dt produces spikes 10 to 30 times the supply: a DC 24V relay coil swings ±200 to 400V for tens of microseconds. Victims: PLC transistor outputs rated 50V, arcing relay contacts, and any electronics sharing the supply. In cabinets full of drives and servos, unexplained output failures trace back to this more often than to anything else.
DC coils take an anti-parallel flyback diode, clamping the spike to −0.7V at the cost of a 5 to 15ms release delay; when fast release matters, a 33 to 39V zener in series with a diode clamps at −36V and releases within 2ms. AC coils cannot share a diode (it would conduct on both half-cycles) - fit an RC snubber, 0.1 to 0.47µF X2 in series with 100 to 470Ω, directly across the coil terminals, and another across contacts that break inductive loads.
| Load type | Suppressor | Values | Result |
|---|---|---|---|
| DC24V relay coil | 1N4007 flyback diode | Cathode to positive | −0.7V spike, 5~15ms release |
| DC24V fast release | 33~39V zener + diode | Series, anti-parallel | −36V clamp, under 2ms |
| AC220V contactor coil | RC 0.47µF X2 + 330Ω | Across coil terminals | Spike within 2x supply |
| Contact breaking load | RC 0.1µF + 100Ω | Across the contact | Less arcing, longer life |
| PLC transistor output | One of the above, always | Match the load | Output life doubles |
| Solenoid DC coil | Diode or varistor 14D | Clamps near 40V | Simple and robust |
Cabinet motto: every coil gets a suppressor - diodes for DC, RC for AC - mounted at the coil terminals, not the far end of the terminal rail. When PLC outputs die in batches, find the naked coil first.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overvoltage protection in control circuits per GB/T 5226.1 (IEC 60204-1); varistor specification per GB/T 10193. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.