A contactor snaps closed on power and drops out without it, but what happens inside? This page dissects the electromagnet, contact system and arc chute, and explains the shading ring and coil burnouts.
The electromagnet consists of coil, core and armature. An AC coil limits current by impedance, and the inrush at pickup with the large air gap reaches 5 to 15 times the holding current, capping the operating rate at a few hundred to about 1200 operations per hour. A shading ring embedded in the core face splits the flux into two out-of-phase components so the pull never reaches zero at current zero; without it the armature buzzes 100 times a second, noisy and destructive.
Main contacts are double-break bridges in silver alloys such as AgCdO or AgSnO2 for weld resistance, from 9 to 800 A, with auxiliary NO/NC pairs of 5 to 10 A. Breaking an AC arc relies on current zero, but the fresh gap ionises easily and restrikes, so contactors above about 20 A wear arc chutes that split the arc into series segments, raising arc voltage. Contact pressure and overtravel are design-set; check them with feeler gauges on overhaul, since low pressure overheats and high pressure starves the magnet.
Coils burn for three reasons: supply beyond ±10 percent of rated, which either leaves the armature chattering at large gap or saturates the core; mechanical sticking from dirty pole faces or worn guides keeping the inrush flowing; and damp insulation failing turn to turn. Bench checks: operate the armature by hand, compare coil resistance with a sister unit within 10 percent, and listen for buzz, which points to the pole face or a cracked shading ring. Match the coil voltage class to the control circuit when replacing.
| Part | Healthy state | Fault sign | Usual cause |
|---|---|---|---|
| Coil | Steady holding current | Overheats, burns | Voltage off-nominal, sticking |
| Pole face | Flat, clean, thin film | Noise and vibration | Dirt, broken shading ring |
| Main contacts | Silvery, light oxide | Welded, eroded | Overload, frequent starting |
| Auxiliary contacts | Positive make-break | Poor contact | Oxidation, low pressure |
| Arc chute | Intact | Phase-to-phase flash | Cracked and not replaced |
| Mechanism | Free movement | Jamming, refusal | Debris, guide wear |
Select by utilisation category and operating rate, insulation-test coil to contacts at 1 MΩ minimum with a 500 V megger before fitting, and during patrols listen for noise and feel the coil: a sudden buzz usually means the shading ring or pole face is failing.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 14048.4 for electromechanical contactors and IEC 60204-1 for machinery safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.