Fuse types and common model numbers explained

Fuse model numbers look messy, but each family has a fixed role: line protection, motor circuits, or semiconductor protection. This page sorts the common types and shows what each one can and cannot do.

1. How it works

Low-voltage fuses split by duty: gG full-range types protect cables and distribution against both overload and short circuit; aM motor types deliberately ride through 6 to 7 times inrush and handle short circuits only, leaving overload to the thermal relay; aR/UR ultra-fast types (RS0, RS3) protect thyristors and IGBTs with a tiny I²t, clearing within milliseconds.

2. Practice and pitfalls

Common constructions: RT18/RT28 cylindrical cartridge fuse holders for 10x38 and 14x51 tubes, RL1 screw-in types with a striker indicator, NT (NH) blade fuses from NT00 to NT3 for 160 to 1250A boards, and RO15/RS0 fast fuses for power electronics. Never substitute copper wire, and never fit an aM element where a gG is specified - overload protection simply disappears.

3. Common fuse families quick table

FamilyTypical modelsRating rangeTypical use
Cartridge holderRT18, RT282~100AControl circuits, small boards
Screw-inRL1, RL62~200AMachine tools, motor circuits
Blade NHNT00~NT3 (RT16/17)4~1250ADistribution boards
Ultra-fastRS0, RS3, RO1510~700AThyristors, drives, rectifiers
Miniature5x20, 6.3x320.1~15AInstruments, power boards
PV dedicatedgS 10x38 PV1~32AString DC protection

4. Notes

Selection order: duty class first (gG, aM or fast), then current rating, then confirm voltage and breaking capacity against the prospective short-circuit current at the installation point. Stock spare links per complete model, never loose mixed bins.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Low-voltage fuse general rules per GB 13539.1 (IEC 60269-1); semiconductor protection per GB/T 13539.4. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① aM link fitted as gG:no overload tripping, cable cooks at low overcurrent
② Copper wire as a fuse link:zero breaking capacity, the tube explodes on short circuit
③ Breaking capacity below fault level:the fuse bursts and takes out the whole board

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.