Schneider LRD thermal overload relay models and setting ranges

The digit at the end of an LRD model number is its current window. This page lists the common LRD ranges and shows how to match them to a motor nameplate current in three steps.

1. How it works

LRD relays follow the TeSys scheme: LRD-04 covers 0.4 to 0.63A, LRD-08 covers 2.5 to 4A, LRD-14 covers 7 to 10A, LRD-21 covers 12 to 18A and LRD-33 covers 23 to 32A. Pick the window where the nameplate current sits within the middle third of the scale; values hugging either end invite nuisance trips or a relay that never operates.

2. Practice and pitfalls

For a 4kW four-pole motor at roughly 8.7A, choose LRD-14 and set the dial to 8.7 before locking it. In star-delta starters, set to 0.58 times line current when the relay sits in the winding circuit. Above 40 degrees ambient, trim the setting down about 1 percent per 3 degrees, and confirm the relay clips onto the matching TeSys contactor frame before ordering.

3. LRD setting range quick table

ModelSetting range AContactorTypical motor
LRD-04C0.4~0.63LC1D090.09~0.12kW
LRD-08C2.5~4LC1D09/D180.75~1.5kW
LRD-14C7~10LC1D09~D183~4kW 4-pole
LRD-21C12~18LC1D18~D255.5~7.5kW
LRD-25C17~25LC1D25~D327.5~11kW
LRD-33C23~32LC1D32~D3811~15kW

4. Notes

Procedure: copy the nameplate current, find the window, keep the dial in the middle third. Before reusing a pulled LRD, verify both the range and the reset mode - manual and automatic versions are not interchangeable in remote auto-restart circuits.

5. References

The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overload relay requirements per GB/T 14048.4 (IEC 60947-4-1); assembly practice per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.

6. Cautions

⚠️ Three common pitfalls:
① Dial set near the upper limit:trip tolerance may leave it silent while the motor cooks
② Dial not locked:panel vibration shifts the setting, intermittent trips follow
③ No ambient correction above 40C:the bimetal pre-bends and trips all summer

Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.