The digit at the end of an LRD model number is its current window. This page lists the common LRD ranges and shows how to match them to a motor nameplate current in three steps.
LRD relays follow the TeSys scheme: LRD-04 covers 0.4 to 0.63A, LRD-08 covers 2.5 to 4A, LRD-14 covers 7 to 10A, LRD-21 covers 12 to 18A and LRD-33 covers 23 to 32A. Pick the window where the nameplate current sits within the middle third of the scale; values hugging either end invite nuisance trips or a relay that never operates.
For a 4kW four-pole motor at roughly 8.7A, choose LRD-14 and set the dial to 8.7 before locking it. In star-delta starters, set to 0.58 times line current when the relay sits in the winding circuit. Above 40 degrees ambient, trim the setting down about 1 percent per 3 degrees, and confirm the relay clips onto the matching TeSys contactor frame before ordering.
| Model | Setting range A | Contactor | Typical motor |
|---|---|---|---|
| LRD-04C | 0.4~0.63 | LC1D09 | 0.09~0.12kW |
| LRD-08C | 2.5~4 | LC1D09/D18 | 0.75~1.5kW |
| LRD-14C | 7~10 | LC1D09~D18 | 3~4kW 4-pole |
| LRD-21C | 12~18 | LC1D18~D25 | 5.5~7.5kW |
| LRD-25C | 17~25 | LC1D25~D32 | 7.5~11kW |
| LRD-33C | 23~32 | LC1D32~D38 | 11~15kW |
Procedure: copy the nameplate current, find the window, keep the dial in the middle third. Before reusing a pulled LRD, verify both the range and the reset mode - manual and automatic versions are not interchangeable in remote auto-restart circuits.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Overload relay requirements per GB/T 14048.4 (IEC 60947-4-1); assembly practice per GB/T 5226.1. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.