You can profile an induction motor without dismantling it: the no-load test separates iron and friction losses, the locked-rotor test gives the short-circuit parameters. This page covers procedure, calculations and pass criteria, useful before and after a rewind.
Run the motor uncoupled at rated voltage and frequency. The input power P0 splits into stator copper loss 3·I0²·R1, iron loss and friction-plus-windage. Step the voltage down from 1.2 times rated in five to seven points, plotting P0 − 3·I0²·R1 against U². Extrapolating the straight line to U² = 0 gives the mechanical loss as the intercept; the rest is iron loss. No-load current should sit at 20 to 50 percent of rated; above 50 percent points at an oversize air gap or too few turns.
For the locked-rotor test, lock the shaft, start from 0.2 to 0.3 of rated voltage and raise it until the current nears rated. With slip equal to 1 the machine behaves like a shorted transformer: Rk = Pk/(3·I²), Zk = U/(√3·I) converted to phase values, Xk = √(Zk² − Rk²). From these you estimate the starting current multiple. Abnormally high current suggests too few turns or a large air gap; low current can mean cracked rotor bars raising rotor impedance.
Use both tests for acceptance and diagnosis. Compare no-load current, no-load loss and locked current against the nameplate; no-load loss 20 percent above sister machines flags poor core quality or eccentric assembly. Three-phase no-load current imbalance beyond 10 percent, or current ripple while hand-turning the rotor, indicts the winding or broken bars. Keep each locked run under 10 seconds and let the winding cool between runs.
| Item | Normal range | High means | Low means |
|---|---|---|---|
| No-load current | 20~50% of rated | Large gap, few turns | Weak flux design |
| No-load loss | On par with sisters | Poor core, eccentricity | Metering or wiring error |
| No-load imbalance | Under 10% | Winding turn fault | Supply or meter issue |
| Locked current | Design multiple ±20% | Few turns, big gap | Possible broken bars |
| Locked torque | 1~2.2 of rated | Over-saturated design | Rotor circuit defect |
| Short-circuit Rk | Matches winding temp | Bar contact resistance | Measurement error |
Keep a test card for every critical motor with no-load current, no-load loss and locked current before and after repair; drift on the card is an early warning. Make sure the rotor is mechanically locked, not just roped, before energising.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: See GB/T 1032 for three-phase induction machine test methods and IEC 60204-1 for machinery safety. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.