Phase loss is the top motor killer: it locks a stopped motor with a hum, and burns a running one within minutes. This page lists the four causes and a layered detection routine.
One phase open means trouble. By frequency: a single blown fuse, a burnt or welding contactor pole, a loose or oxidized terminal, or an upstream line or transformer fault. Stopped motors cannot start - just a 4 to 6 times rated hum; running motors lean on two phases, whose current climbs to 1.7 to 2 times rated, cooking windings in minutes.
Detection, in order: measure the three line voltages (UAB, UBC, UCA), each about 380V; two lines reading near zero locate the open phase, then check line-to-earth to identify it. No-load readings lie - a floating contactor still shows full voltage unloaded, so measure running current with a clamp meter; a spread over 10 percent or one dead phase confirms it. Then inspect contactor tips (drop above 100mV loaded means service them) and work upstream if the board is clean. Protection: use phase-failure thermal relays or dedicated phase-loss relays (trip within 3 seconds), prefer breakers over single-phase fuses, and always find the root cause before fitting the replacement motor.
| Checkpoint | Normal | With phase loss | Tool |
|---|---|---|---|
| Three line voltages | About 380V each | One pair near 0V | Multimeter 500V |
| Line-to-earth voltages | About 220V each | Open phase abnormal | Multimeter 500V |
| Running currents | Balanced | Two phases at 1.7~2x, one zero | Clamp meter |
| Contactor drop | Millivolts | Above 100mV loaded | mV range |
| Terminal temperature | Near ambient | Hot spots | IR gun |
| Start attempt | Starts normally | Hums, will not turn | Observe + clamp |
Routine: voltage first, current second; local board first, upstream second; unloaded readings never clear a fault. Low phase current and a hot terminal are the early warnings - catch them at inspection and the motor lives.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Motor protection per GB/T 5226.1; voltage unbalance limits per GB/T 15543; LV breakers per GB/T 14048.2. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.