With drives and switch-mode supplies everywhere, current is no longer sinusoidal. This page explains harmonic decomposition, true RMS, and why ordinary meters lie inside drive cabinets.
Any periodic waveform decomposes into the 50Hz fundamental plus integer multiples: 3rd at 150Hz, 5th at 250Hz. Symmetric waveforms contain only odd harmonics; a square wave carries 1/3, 1/5, 1/7 components. Typical offenders: drive input currents dominated by the 5th and 7th with THD of 60 to 100 percent, and clusters of switch-mode supplies pushing the 3rd harmonic into the neutral.
RMS is the root-sum-square of all components: 10A fundamental plus 4A of 5th gives √(10²+4²) ≈ 10.8A. The meter trap: average-responding multimeters are calibrated for sine waves and read PWM or square waves 20 to 40 percent wrong - only a true-RMS instrument with adequate bandwidth counts. And the neutral surprise: 3rd harmonics add arithmetically in the neutral, which can carry 1.7 times phase current, so size it up. Remedies: line reactors or EMC filters on drive inputs, tuned branches for the 5th and 7th, and detuned (7 percent reactor) capacitor banks in harmonic environments.
| Equipment | Main harmonics | Typical THD | Remedy |
|---|---|---|---|
| VFD input | 5th, 7th | 60~100% | Line reactor or filter |
| Six-pulse rectifiers | 5th, 7th, 11th | 30~80% | More pulses or filtering |
| SMPS clusters | 3rd | Above 80% | Oversize the neutral |
| Welders, arc furnaces | 2nd, 3rd, 5th | Varying | Filters plus dynamic compensation |
| Electronic ballasts | 3rd | 15~30% | Filter on large installs |
| Resistive heating | Almost none | Under 5% | No treatment needed |
Field rules: inside drive cabinets, ask about meter bandwidth before believing a reading; abnormal neutral current, think 3rd harmonic. Bulging capacitor banks usually miss their detuning reactors - fit them before replacing cans again.
The quantities and component characteristics discussed here follow current national standards and the corresponding IEC documents: Public grid harmonic limits per GB/T 14549; measurement methods per the IEC 61000-4 series. Always check the device datasheet and the product design file for ratings and derating.
Locate the issue with the approach above, then confirm with measurements; safety-related circuits must follow the standards and manufacturer requirements.